K-Box
(INF 2201)
Last updated
(INF 2201)
Last updated
The CAN Connectors are 1x Male and 1x Female 9-pin Standard D Type Connectors with nuts.
Pin No | Pin Function |
Pin 1 | Digital Output 4 or +4.5V Instrumentation Supply Voltage, ensure that current draw is not more than 100mA |
Pin 2 | CAN Bus Low Signal |
Pin 3 | Ground |
Pin 4 | Digital Input or Output 1 - Do not apply voltages outside of the 0 to +12V range when used as an input. When used as an Output, ensure that the current drawn is not more than 100mA. More information on the use of this pin can be found in Appendix 2 and 3 |
Pin 5 | Power Ground |
Pin 6 | Digital Input or Output 3 |
Pin 7 | CAN Bus High Signal |
Pin 8 | Digital Input or Output 2 - Do not apply voltages outside of the 0 to +12V range when used as an input. When used as an Output, ensure that the current drawn is not more than 100mA. More information on the use of this pin can be found in Appendix 2 and 3 |
Pin 9 | 4.5-36V Supply Voltage |
The ADC Connector is a Male 25-pin Standard D-Type Connector with nuts.
Pin No | Pin Function |
Pin 1 | +24V Output - ensure that the current drawn is not more than 75mA |
Pin 2 | +5V Output - ensure that the current drawn is not more than 75mA |
Pin 5 | Analog Ground |
Pin 6 | Analog Input 0 + ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 7 | Analog Input 1 + ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 8 | Analog Input 2 + ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 9 | Analog Input 3 + ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 10 | Analog Input 4 + ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 11 | Analog Input 5 + ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 12 | Analog Input 6 + ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 13 | Analog Input 7 + ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 14 | Ground Out |
Pin 15 | Ground Out |
Pin 17 | Analog Ground |
Pin 18 | Analog Input 0 - ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 19 | Analog Input 1 - ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 20 | Analog Input 2 - ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 21 | Analog Input 3 - ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 22 | Analog Input 4 - ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 23 | Analog Input 5 - ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 24 | Analog Input 6 - ve (do not apply voltages outside the voltage range the K-Box is configured for). |
Pin 25 | Analog Input 7 - ve (do not apply voltages outside the voltage range the K-Box is configured for). |
The Thermocouple Connectors on the K-Box are miniature-size flat-type sockets.
IEC Connector | Pin Function |
Top | + Signal from the Thermocouple |
Bottom | K Signal from the Thermocouple |
The dimensions of the Male Flat Type Miniature Size Thermocouple Plug that you would plug into it are as follows: